Features of the Onguard 800 System Input Vote Module
- Module can occupy same rack as three channel model 1440 Input Module
- Accepts two independent inputs applicable to any dry input contact device, such as optical, smoke, or heat detectors
- Optional time delays are adjustable from 0 to 15 seconds for each input
- Auxiliary form C fire relay can be independently voted
- Relay is selective for latching or non-latching
- Memory feature allows alarm LED to remain on during alarm and blinks when alarm clears
- Input voting capability has independent control transferred to Alarm Module and Release Module
- Recessed detector test switch option able to source or sink current
- Individual open collector outputs for each channel operate in failsafe mode
- Detector fused power output and reset switch
- All field wiring supervised per NFPA requirement
|
|
|
|
Onguard 800 System Input Vote Module
Model 1530 Input Module is a primary detector module that accepts two independent dry relay contacts from initiating devices. This module can vote between its local two input channels as well as other Input Vote Modules, requiring the combination of up to four valid alarms to confirm the alarm condition. The voting configuration can trip the Alarm, Release and Relay Modules based on DIP switch settings.
Inputs are individually monitored for a fault condition. A fault will be an-nounced with its respective yellow fault LED and will activate the Fault Module. The detector power output fuse is monitored and rated at 3A.
Approvals
Specifications of the Onguard 800 System Input Vote Module
Electrical |
Approved operating voltage: |
20 - 28 VDC redundant power sources |
Operating current: |
30mA quiescent, 54mA alarm |
Detector power source fuse rating: |
3 amps |
Dry relay outputs: |
5 amps, 30 VDC resistive, 250 VAC
Output relay sealed and contains an inert gas
Auxiliary fire relay is customer selective for latching or non latching
Relay is form C configuration |
Mechanical |
Size: |
1.04"W X 3.46"H X 6.4"D |
Weight: |
3.7 ounces |
Environment |
Ambient operating temperature: |
0°F to 150°F
-17°C to 65°C
90% humidity non-condensing |
Packaging and exposure: |
NEMA 1 |
Part Number |
Description |
800-1530 |
Input Vote Module |
800-1211 |
End of line resistors, 2 supplied |
800-1378 |
Test switch rod |
800-1186 |
System manual |
Onguard 800 Series Gas and Fire Control Panel Components
|